The KRONAS UNIC NEW solid fuel boiler can rightfully be classified as a long-burning boiler. With a large firebox and a multi-pass, four-shelf heat exchanger, as well as secondary air nozzles, the UNIC NEW series boilers offer the highest performance in their class. The firebox and heat exchanger are made of 6mm thick sheet metal, ensuring long-lasting operation. The NEW model has received a number of design changes, including:
Ergonomic design;
Sloping loading doors;
Round chimney for easy installation;
Possibility of using a mechanical draft regulator;
The presence of a mechanical thermometer.
The KRONAS UNIC NEW boiler's primary fuel is wood (of any type and moisture content), coal, and all types of fuel briquettes. Like other KRONAS boiler models, it can be equipped with various types of automation, expanding its range of applications.
| Parameter | Units of measurement | Standard for the Kronas UNIC New boiler |
| Nominal boiler power | kW | 17 | 22 | 27 | 35 | 50 | 62 | 75 | 98 | 125 | 150 |
| Estimated heating area | m2 | 170 | 220 | 270 | 350 | 500 | 620 | 750 | 980 | 1250 | 1500 |
| Fuel | — | firewood, anthracite, coal |
| Heat exchanger area | m2 | 2.9 | 3.3 | 3.8 | 4.2 | 5.4 | 6.2 | 7.1 | 9.3 | 10.2 | 11.3 |
| Efficiency, not less than | % | 83 |
| One-time fuel loading | kg | 44 | 53 | 62 | 84 | 113 | 142 | 180 | 261 | 342 | 410 |
| Duration of combustion of a single fuel load | hour | 8-24 |
| Firebox dimensions |
| depth | mm | 400 | 470 | 510 | 590 | 610 | 740 | 710 | 970 | 970 | 970 |
| width | mm | 380 | 380 | 400 | 400 | 450 | 450 | 550 | 550 | 700 | 770 |
| volume | dm3 | 88 | 98 | 122 | 145 | 214 | 260 | 305 | 416 | 577 | 635 |
| Water capacity of the boiler | l | 92 | 110 | 132 | 165 | 198 | 230 | 290 | 350 | 390 | 420 |
| Weight of the boiler without water | kg | 340 | 375 | 410 | 455 | 650 | 700 | 810 | 970 | 1060 | 1150 |
| Required flue gas draft | By | 23-35 |
| Flue gas temperature at the boiler outlet | ° C | 100-180 |
| Recommended minimum water temperature | ° C | 58 |
| Maximum water temperature | ° C | 90 |
| Nominal (maximum working) water pressure | MPa | 0.15-0.20 |
| Test water pressure, no more | MPa | 0.30 |
| Power consumption, no more than | Tue | 85 | 85 | 85 | 105 | 160 | 160 | 160 | 175 | 175 | 205 |
| Overall dimensions of the boiler |
| IN | mm | 680 | 680 | 700 | 725 | 775 | 775 | 900 | 900 | 1060 | 1150 |
| B1 | mm | 580 | 580 | 600 | 600 | 650 | 650 | 750 | 750 | 900 | 970 |
| H | mm | 1610 | 1610 | 1640 | 1715 | 2065 | 2065 | 2090 | 2090 | 2175 | 2175 |
| H1 | mm | 1490 | 1490 | 1510 | 1510 | 1850 | 1850 | 1850 | 1850 | 1935 | 1935 |
| H2 | mm | 1235 | 1235 | 1265 | 1245 | 1575 | 1575 | 1560 | 1560 | 1645 | 1655 |
| H3 | mm | 295 | 295 | 270 | 270 | 275 | 275 | 310 | 310 | 310 | 310 |
| L | mm | 885 | 955 | 995 | 1125 | 1170 | 1300 | 1275 | 1535 | 1535 | 1535 |
| L1 | mm | 685 | 755 | 795 | 875 | 910 | 1040 | 1010 | 1270 | 1270 | 1270 |
| Loading door size |
| height | mm | 215 | 215 | 245 | 245 | 300 | 300 | 300 | 300 | 300 | 300 |
| width | mm | 335 | 335 | 355 | 355 | 360 | 360 | 460 | 460 | 460 | 460 |
| Connecting (external) dimensions of the hog | mm | 178 | 178 | 178 | 219 | 219 | 245 | 245 | 299 | 299 | 299 |
| Diameter of the supply and return network water pipes (DN) | mm | 50 | 50 | 50 | 50 | 50 | 50 | 65(FL) | 65(FL) | 80(FL) | 80(FL) |
| Diameter of the safety valve pipes (DN) | mm | 15 | 15 | 15 | 15 | 20 | 20 | 20 | 20 | 20 | 20 |
| Recommended chimney parameters |
| cross-sectional area | cm2 | 256 | 256 | 256 | 380 | 380 | 490 | 490 | 706 | 706 | 706 |
| inner diameter | mm | 180 | 180 | 180 | 220 | 220 | 250 | 250 | 300 | 300 | 300 |
| height (minimum permissible) | m | 5 | 5 | 5 | 5 | 6 | 6 | 7 | 7 | 7 | 8 |
Source link: